What a busbar is

An aluminium busbar, or flat bar, is extruded stock of rectangular section with a large width and a small thickness. Busbars for electrical engineering are made to GOST 15176. Aluminium conducts current well and is much lighter than copper, so busbars for distributing electricity in cabinets, boards and switchgear are made of it, as well as frames, bars and cladding.

Sizes and alloys

The size of a busbar is written as thickness and width, for example 2 by 10 mm. In the catalog the thickness varies from 2 to 20 mm and the width from 10 to 200 mm; the length is mostly 6000 mm, for a few items 3000 mm. For electrical engineering the alloy AD31 (6060 T5) is used: it has good electrical conductivity and sufficient strength. For mechanical tasks D16ChT and 1420T are also found.

Where it is used

  • distribution cabinets, panels and substations;
  • grounding and potential equalization;
  • frames, strips, cladding and brackets;
  • heat exchangers and cooling radiators;
  • decorative profiles and furniture elements.

Joining busbars

Busbars are joined with bolts through overlays. The contact surfaces are cleaned of the oxide film and at once protected with contact grease so that the film does not grow again. Aluminium creeps under the pressure of a bolt, so disc spring washers are placed under the nuts to maintain the tightening force. The junction of aluminium with copper is made through special transition elements, otherwise in a damp environment the contact is destroyed by galvanic corrosion.

Cutting and bending

A busbar is cut with a circular saw or a guillotine, and after cutting the edges are cleaned so that there are no sharp burrs. It can be bent edgewise or flatwise. The bending radius depends on the thickness and alloy: too small a radius causes cracks, especially in hard tempers. Holes for bolts are drilled and not punched if the busbar is thick.

Current and heating

The permissible current of a busbar depends on the cross-section area, the cooling conditions and the ambient temperature, and not only on the width. The busbar is placed on edge so that it gives off heat better, and a gap for ventilation is left between busbars. Joints heat up most: a badly cleaned or loosely tightened joint raises resistance and overheats. The calculation is made by the electrician according to the project norms, not by the catalog.

Receiving and storage

On receiving, the thickness and width, straightness, edges and the absence of deep scratches are checked. Busbars are stored in a dry place on level supports, interleaved with spacers so as not to spoil the surface. The contact areas are cleaned anew before joining, even if the busbar lay for a short time, because the oxide film forms within minutes.

Common mistakes

  • joining aluminium to copper without a transition element;
  • not cleaning the contact of the oxide film;
  • taking a busbar by analogy with a copper one without recalculating the section.

How to choose and what to state

  • the thickness and width of the busbar for the current and the structure;
  • the alloy and temper;
  • the length or the size of blanks;
  • how the busbar will be joined with copper or other busbars.

Related sections

Need a consultation?

Leave a request — we'll call you and help with selection and calculation.